What is the outside diameter of 14 inch pipe?
14 inch (NPS 14, DN 350) pipe has an outside diameter of 355.6 mm (14 in). The OD stays the same for every schedule; a heavier schedule only reduces the inside diameter.
NPS 14 · DN 350
14 inch nominal pipe has a fixed outside diameter of 355.6 mm (14 in). B36.10M and B36.19M list 13 wall thicknesses for this size, from 3.96 mm to 35.71 mm. Schedule 40 gives a 333.34 mm bore and schedule 80 a 317.5 mm bore.
Metric
| Schedule | Wall mm | ID mm | Mass kg/m | Water-filled kg/m | Flow area mm² |
|---|---|---|---|---|---|
| Sch 5S / Sch 5 | 3.96 | 347.68 | 34.34 | 129.28 | 94,940 |
| Sch 10S | 4.78 | 346.04 | 41.36 | 135.41 | 94,046 |
| Sch 10 | 6.35 | 342.90 | 54.69 | 147.04 | 92,347 |
| Sch 20 | 7.92 | 339.76 | 67.91 | 158.57 | 90,664 |
| Sch 30 / STD / Sch 40S | 9.53 | 336.54 | 81.33 | 170.28 | 88,954 |
| Sch 40 | 11.13 | 333.34 | 94.55 | 181.82 | 87,270 |
| XS / Sch 80S | 12.70 | 330.20 | 107.40 | 193.03 | 85,634 |
| Sch 60 | 15.09 | 325.42 | 126.72 | 209.89 | 83,172 |
| Sch 80 | 19.05 | 317.50 | 158.11 | 237.28 | 79,173 |
| Sch 100 | 23.83 | 307.94 | 194.98 | 269.46 | 74,477 |
| Sch 120 | 27.79 | 300.02 | 224.66 | 295.36 | 70,695 |
| Sch 140 | 31.75 | 292.10 | 253.58 | 320.59 | 67,012 |
| Sch 160 | 35.71 | 284.18 | 281.72 | 345.15 | 63,427 |
Imperial
| Schedule | Wall in | ID in | Weight lb/ft | Flow area in² |
|---|---|---|---|---|
| Sch 5S / Sch 5 | 0.156 | 13.688 | 23.09 | 147.153 |
| Sch 10S | 0.188 | 13.624 | 27.76 | 145.780 |
| Sch 10 | 0.250 | 13.500 | 36.75 | 143.139 |
| Sch 20 | 0.312 | 13.376 | 45.65 | 140.521 |
| Sch 30 / STD / Sch 40S | 0.375 | 13.250 | 54.62 | 137.886 |
| Sch 40 | 0.438 | 13.124 | 63.50 | 135.276 |
| XS / Sch 80S | 0.500 | 13.000 | 72.16 | 132.732 |
| Sch 60 | 0.594 | 12.812 | 85.13 | 128.921 |
| Sch 80 | 0.750 | 12.500 | 106.23 | 122.718 |
| Sch 100 | 0.938 | 12.124 | 130.98 | 115.447 |
| Sch 120 | 1.094 | 11.812 | 150.93 | 109.581 |
| Sch 140 | 1.250 | 11.500 | 170.37 | 103.869 |
| Sch 160 | 1.406 | 11.188 | 189.29 | 98.309 |
Walls shared by more than one designation are merged into one row (for example STD / Sch 40 / 40S). Inch walls are converted from the millimetre values and rounded to three decimals.
Questions
14 inch (NPS 14, DN 350) pipe has an outside diameter of 355.6 mm (14 in). The OD stays the same for every schedule; a heavier schedule only reduces the inside diameter.
14 inch schedule 40 pipe has a nominal wall of 11.13 mm (0.438 in) and an inside diameter of 333.34 mm (13.124 in). Plain-end carbon steel mass is about 94.55 kg/m (63.5 lb/ft).
14 inch schedule 80 pipe has a nominal wall of 19.05 mm (0.75 in) and an inside diameter of 317.5 mm (12.5 in). Plain-end carbon steel mass is about 158.11 kg/m (106.23 lb/ft).
14 inch schedule 160 pipe has a nominal wall of 35.71 mm (1.406 in) and an inside diameter of 284.18 mm (11.188 in). Plain-end carbon steel mass is about 281.72 kg/m (189.29 lb/ft).
No. For 14 inch pipe, STD has a 9.53 mm wall while schedule 40 has a 11.13 mm wall. STD and schedule 40 only coincide up to NPS 10.
Plain-end carbon steel mass per metre is 0.0246615 x (OD - t) x t with OD and wall t in mm (ASME B36.10M). For imperial units use 10.69 x (OD - t) x t with inches, giving lb/ft. Stainless steel is roughly 2% heavier because of its higher density.
Nearby sizes
NPS 8 · DN 200 · OD 219.1 mm · 12 walls
Open sizeNPS 10 · DN 250 · OD 273 mm · 11 walls
Open sizeNPS 12 · DN 300 · OD 323.8 mm · 13 walls
Open sizeNPS 16 · DN 400 · OD 406.4 mm · 12 walls
Open sizeNPS 18 · DN 450 · OD 457 mm · 14 walls
Open sizeNPS 20 · DN 500 · OD 508 mm · 12 walls
Open size